Available: 8am-7pm 93650628



Free standard shipping on orders over $150
We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.
When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.
Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.
The Hercules 2.5KG Automatic Ceiling Fire Extinguisher is designed for fixed installation above potential fire hazards, providing automatic fire suppression without manual activation.
Equipped with a heat-activated glass bulb sprinkler head, the extinguisher automatically discharges ABC dry powder when the surrounding temperature reaches its activation threshold of 68°C.
Suitable for industrial, commercial and marine environments, particularly in enclosed areas requiring additional fire protection.
Automatic Fire Suppression – Heat-activated sprinkler head automatically releases the extinguishing agent.
ABC Dry Powder – Multi-purpose extinguishing agent suitable for various fire hazards.
68°C Activation Temperature – Fitted with a temperature-sensitive glass bulb sprinkler head.
Ceiling-Mounted Design – Allows fixed overhead installation directly above potential fire hazards.
Stored Pressure System – Utilises nitrogen as the propellant.
Rapid Discharge – Discharge time of approximately 3 seconds.
Compact Construction – Suitable for installation in areas with limited space.
| Brand | Hercules |
| Model | FT01-067-00 |
| Part Number | FEL-FT-A25 |
| Capacity | 2.5kg |
| Extinguishing Agent | ABC Dry Powder |
| Propellant | Nitrogen |
| Operation Method | Stored Pressure |
| Discharge Time | 3 seconds |
| Body Diameter | 180mm |
| Total Height | 260mm |
| Total Weight | 4.2kg |
| Bulb Activation Temperature | 68°C |
| Optional Bulb Temperatures | 57°C / 79°C / 93°C / 144°C |
| Working Pressure | 12 bar |
| Test Pressure | 25 bar |
| Fire Rating | 5A : 6B |
| Class A Coverage | 0.35m² |
| Class B Coverage | 0.47m² |
| Tested Installation Height | 2.5m |
Note: Fire rating and coverage were tested at a height of 2.5m.
Mount centrally above the area requiring protection, with the discharge nozzle pointing vertically downwards.
The recommended installation height is 2.5m above the potential fire hazard in a non-vibrating environment.
Installation should be carried out by a qualified professional in accordance with applicable fire safety requirements.